Oyster Creek Reactor: Bad Nuclear Vibrations 

Union of Concerned Scientists DAVE LOCHBAUM, DIRECTOR, NUCLEAR SAFETY PROJECT | JUNE 13, 2017The Oyster Creek Nuclear Generating Station near Forked River, New Jersey is the oldest nuclear power plant operating in the United States. It began operating in 1969 around the time Neil Armstrong and Buzz Aldrin were hiking the lunar landscape.

Oyster Creek has a boiling water reactor (BWR) with a Mark I containment design, similar to the Unit 1 reactor at Fukushima Daiichi. Water entering the reactor vessel is heated to the boiling point by the energy released by the nuclear chain reaction within the core (see Figure 1). The steam flows through pipes from the reactor vessel to the turbines. The steam spins the turbines connected to the generator that produces electricity distributed by the offsite power grid. Steam discharged from the turbines flows into the condenser where it is cooled by water drawn from the Atlantic Ocean, or Barnegat Bay. The steam vapor is converted back into liquid form. Condensate and feedwater pumps supply the water collected in the condenser to the reactor vessel to repeat the cycle………

Bad Vibrations

In the early morning hours of November 20, 2016, the operators at Oyster Creek were conducting the quarterly test of the turbine control system. With the reactor at 95 percent power, the operator depressed a test pushbutton at 3:26 am per the procedure. The plant’s response was unexpected. The positions of the control valves and bypass valves began opening and closing small amounts causing the reactor pressure to fluctuate. Workers in the turbine building notified the control room operators that the linkages to the valves were vibrating. The operators began reducing the reactor power level in an attempt to stop the vibrations and pressure fluctuations.

The reactor automatically shut down at 3:42 pm from 92 percent power on high neutron flux in the reactor. Workers later found the linkage for control valve #2 had broken due to the vibrations and the linkage for control valve #4 had vibrated loose. The linkages are “mechanical arms” that enable the turbine control system to reposition the valves. The broken and loosened linkages impaired the ability of the control system to properly reposition the valves.

These mechanical malfunctions prevented the EHC system from properly controlling reactor pressure during the test and subsequent power reduction. The pressure inside the reactor vessel increased. In a BWR, reactor pressure increases collapse and shrink steam bubbles. Displacing steam void spaces with water increases the reactor power level. When atoms split to release energy, they also release neutrons. The neutrons can interact with other atoms to causing them to split. Water is much better than steam bubbles at slower down the neutrons to the range where the neutrons best interact with atoms. Put another way, the steam bubbles permit high energy neutrons to speed away from the fuel and get captured by non-fuel parts within the reactor vessel while the water better confines the neutrons to the fuel region.

The EHC system’s problem allowed the pressure inside the reactor vessel to increase. The higher pressure collapsed steam bubbles, increasing the reactor power level. As the reactor power level increased, more neutrons scurried about as more and more atoms split. The neutron monitoring system detected the increasing inventory of neutrons and initiated the automatic shut down of the reactor to avoid excessive power and fuel damage.

Workers attributed the vibrations to a design flaw. A component in the EHC system is specifically designed to dampen vibrations in the tubing providing hydraulic fluid to the linkages governing valve positions. But under certain conditions, depressing the test pushbutton creates a pressure pulse on that component. Instead of dampening the pressure piles, the component reacts in a way that causes the hydraulic system pressure to oscillate, creating the vibrations that damaged the linkages.

The component and damaged linkages were replaced. In addition, the test procedure was revised to avoid performing that specific portion of the test when the reactor is operating. In the future, that part of the turbine valve test will be performed during an outage.

Vibrations Re-Visited

It was not the first time that Oyster Creek was shut down due to problems performing this test. It wasn’t even the first time this decade…..http://allthingsnuclear.org/dlochbaum/oyster-creek-bad-vibrations

Advertisements

June 14, 2017 - Posted by | safety, USA

No comments yet.

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out / Change )

Twitter picture

You are commenting using your Twitter account. Log Out / Change )

Facebook photo

You are commenting using your Facebook account. Log Out / Change )

Google+ photo

You are commenting using your Google+ account. Log Out / Change )

Connecting to %s

%d bloggers like this: